Product Safety Recalls

Product Recall Tracker

Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option

Description: This recall involves Carrier WeatherExpert 6-23 ton, 48/50 series, light commercial rooftop HVAC units intended for use in commercial and institutional buildings and that have a factory installed dehumidification feature. The model numbers are 48/50LC07-26 with an A in the 6th digit and a 0 (zero) in the 14th digit of the model number (e.g., 48LCTA24F2M5-0S1B3). Note that dashes should be counted as digits in the model number. The serial numbers are 1214P to 3317P. The model and serial number can be found on the unit rating plate located on the back of the unit. [Learn More]

About 530 units were affected by this recall.

Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option
Carrier® Recalls to Repair Commercial Rooftop HVAC Units Due to Fire Hazard (Recall Alert)

40/50 series LC rooftop HVAC unit.

Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option Recall Information

Country of OriginMexico
Recall Date03/19/2018
Recall ID8287
Recall Number18731
HazardThe HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard.
InjuriesCarrier has received one report of a fan not shutting off during installation testing. No injuries have been reported.
RemedyPurchasers should immediately contact their Carrier dealer for a free repair, which consists of free replacement and installation of the electronic control board. The firm is contacting all known purchasers.
Remedy OptionRepair
ContactCarrier toll-free at 844-864-8748 from 8 a.m. to 5 p.m. ET Monday through Friday, or online at www.carrier.com and click on “Product Safety Recall” to locate a local Carrier dealer for more information.
Last Updated03/19/2018
Similar To

© 2022 Recall.Report / Contact / Privacy Policy

This site's data is aggregated programmatically and provided "as is" without any representations or warranties, express or implied.
Recall.report is not affiliated with the Consumer Product Safety Commision, FDA, or US government in any way.