Fire Alarm Control Panel

Description: The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings. [Learn More]

About 330 units were affected by this recall.

Fire Alarm Control Panel
Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard

Recalled Bosch fire control panel.

Fire Alarm Control Panel Recall Information

Country of OriginChina
Recall Date02/15/2012
Recall ID1179
Recall Number12721
Product TypeFire or Smoke Alarms
HazardOn all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.
InjuriesNone reported.
RemedyAll distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.
Remedy OptionNew Instructions
ContactFor more information, contact Bosch Security Systems at (800) 289-0096 between 8:00 a.m. and 8:00 p.m. ET or visit service/customer care on the firm’s website at http://www.boschsecurity.us/en-us/ for instructions on how to download software to update the control panels or otherwise address the problems.