Product Safety Recalls

Product Recall Tracker

Square D branded, molded case F and K frame circuit breakers

Description: This recall involves Square D brand models FA, FH, FI and FY one-, two- and three-pole circuit breakers rated 15 to 100 amps, and model KI two- and three-pole circuit breakers rated 110 to 250 amps. The F model breakers were manufactured May 8, 2013 through June 10, 2013 and have date codes 13193 through 13241. The K models were manufactured May 2, 2013 through June 21, 2013 and have date codes 13184 through 13255. The date codes are YYWWD format (example: 13184 = year 2013, week 18, day of the work week 4/ Thursday). The circuit breakers have a yellow label with the words "Square D" or the Square D logo. Model information can be found on the faceplate. [Learn More]

About 28,400 units were affected by this recall.

Square D branded, molded case F and K frame circuit breakers
Schneider Electric Recalls Square D-Brand F and K Frame Circuit Breakers Due to Fire Hazard

FA/FH – 1, 2 & 3 Pole. FI – 2 & 3 Poles and FY – 1 Pole

Square D branded, molded case F and K frame circuit breakers Recall Information

Country of OriginMexico
Recall Date03/18/2014
Recall ID1642
Recall Number14134
Product TypeElectric Wire or Wiring Systems
HazardThe circuit breaker can fail to trip when an overload occurs, posing the risk of fire, burn and electric shock.
InjuriesNone reported.
RemedyConsumers should immediately check to see if they have the recalled circuit breakers. Consumers with uninstalled products will receive a replacement. Installed products will be replaced at no charge to the customer with an allowance of up to $300 per site to cover labor costs.
Remedy OptionReplace
ContactSchneider Electric USA at (800) 634-8730 anytime. Consumers can also visit the firm’s website at www.schneider-electric.us and click on “customer notification” under the popular links category for more information.
Last Updated01/08/2015
Similar To

© 2022 Recall.Report / Contact / Privacy Policy

This site's data is aggregated programmatically and provided "as is" without any representations or warranties, express or implied.
Recall.report is not affiliated with the Consumer Product Safety Commision, FDA, or US government in any way.