Product Safety Recalls

Product Recall Tracker

Effikal Gas Vent Dampers for Allied Engineering Gas Boiler Systems

Description: Gas Vent Dampers Recalled by Effikal Due to Carbon Monoxide Hazard NEWS from CPSC U.S. Consumer Product Safety Commission Office of Information and Public Affairs Washington, DC 20207 FOR IMMEDIATE RELEASE Originally issued October 9, 2008 Last Revised June 02, 2009 Release #09-008 Firm's Recall Hotline: (866) 790-3739 CPSC Recall Hotline: (800) 638-2772 CPSC Media Contact: (301) 504-7908 Note: Weil-McLain vent damper serial numbers changed; new sale dates and stores added. Gas Vent Dampers Recalled by Effikal Due to Carbon Monoxide Hazard WASHINGTON, D.C. - The U.S. Consumer Product Safety Commission, in cooperation with the firm named below, today announced a voluntary recall of the following consumer product. Consumers should stop using recalled products immediately unless otherwise instructed. It is illegal to resell or attempt to resell a recalled consumer product. Name of Product: Automatic Gas Vent Dampers Units: About 45,000 Manufacturer: Effikal LLC, of Orion, Mich. Hazard: The automatic gas vent damper could fail, and if the blocked vent switch does not activate, the vent could leak carbon monoxide (CO). This poses a risk of CO poisoning to consumers. Incidents/Injuries: None reported. Description: The recall involves Effikal RVGP-PC Gas Vent Damper size 4, 5, 6, 7, 8, 9, or 10 which are installed with the gas boiler systems listed below. The vent damper date code is located on a sticker under the motor assembly cap on the plastic base. Serial numbers are located on a label on the side of the damper’s cap. All sizes and models of the RVGP-PC have the same motor assembly with black Effikal caps and black plastic bases. Manufacturer Atmospheric Gas Boiler Models Vent Damper Date Codes Vent Damper Serial Numbers Allied Engineering MG, MS and SG Series 0728 through 0809 3588428 through 3687571 Burnham Series 2b, Series 8h, and Independence except Independence PV 0728-0738 3588428-3647820 Crown AWI, CWI and BSI Series 0728-0809 3588428-3687571 Hydro Therm R/MR, VGA, VS and HW Series 0728-0809 3588428-3687571 Laars JV Series 0728-0809 3588428-3687571 Lochinvar CBN Solution Series 0728-0809 3588428-3687571 RBI Spectrum Series 0728-0809 3588428-3687571 Smith GB and HW Series 0728-0809 3588428-3687571 New Yorker CG and CGS Series 0728-0738 3588428-3647827 Peerless MI, 63 and GM series 0728-0809 3588428-3687571 Raypak Series XV-42-180 Series V-181-260 and 182-261 Series VII-133 0728-0809 3588428-3687571 Union Steam GWA and GSA 0728-0809 3588428-3687571 Weil-McLain CGa, EG, and PFG Series 0728-0738 3538074-3647830 WilliamsonThermoflo GWA and GSA s 0728-0738 3538074-3647830 Sold by: Plumbing and heating wholesale distributors to plumbers and contractors nationwide from August 2007 through July 2008. Vent dampers were also sold by large home improvement stores as part of the gas boiler systems between August 2007 through January 2009 for between $1,000 and $4,000 for the boilers. Manufactured in: United States Remedy: Consumers should immediately stop using the boilers, weather permitting, and contact their installer to confirm they have a recalled vent damper and to receive a free vent damper replacement. Consumer Contact: For additional information, contact Effikal toll-free at (866) 790-3739, or visit the firm’s Web site at www.effikal.com Effikal Automatic Gas Vent Dampers [Learn More]

Effikal Gas Vent Dampers for Allied Engineering Gas Boiler Systems Recall Information

Country of OriginUnited States
Recall Date10/09/2008
Recall ID4931
Recall Number09008
Product TypeVent Pipes
HazardCarbon Monoxide (CO)
Similar To

© 2022 Recall.Report / Contact / Privacy Policy

This site's data is aggregated programmatically and provided "as is" without any representations or warranties, express or implied.
Recall.report is not affiliated with the Consumer Product Safety Commision, FDA, or US government in any way.