Product Safety Recalls

Product Recall Tracker

Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)

Description: This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected. [Learn More]

About 1,000 units were affected by this recall.

Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO

Fire Alarm Panel. ILI-MB-E3-KINETIS Panel

Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3) Recall Information

Country of OriginUnited States
Recall Date03/31/2016
Recall ID6692
Recall Number16134
Product TypeFire or Smoke Alarms
HazardWhen configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
InjuriesNo incidents or injuries have been reported.
RemedyConsumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.
Remedy OptionRepair
ContactGamewell-FCI at 800-274-4324 from 7 a.m. to 7 p.m. ET Monday through Friday or online at www.gamewell-fci.com and click on “Safety Recall” for more information.
Last Updated03/31/2016
Similar To